Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/29/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE A SECONDARY OVERFLOW SENSOR ON EVAP. COIL 2. DO NOT USE PLASTIC DRAIN PIPE WITHIN 6" OF VENT CONNECTOR. 3. EXTEND LOW COMBUSTION AIR VENT TO WITHIN 12" OF FLOOR 4. REPAIR INSULATION ON REFRIGERATION LINE 5. PROVIDE SUPPORT ON DUCT WORK ABOVE FLEX CONNECTOR |