Permit: T08CM01057

Parcel: 129020740

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM01057

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/16/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/29/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE A SECONDARY OVERFLOW SENSOR ON EVAP. COIL
2. DO NOT USE PLASTIC DRAIN PIPE WITHIN 6" OF VENT CONNECTOR.
3. EXTEND LOW COMBUSTION AIR VENT TO WITHIN 12" OF FLOOR
4. REPAIR INSULATION ON REFRIGERATION LINE
5. PROVIDE SUPPORT ON DUCT WORK ABOVE FLEX CONNECTOR