Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08CM01057
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
05/29/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE A SECONDARY OVERFLOW SENSOR ON EVAP. COIL 2. DO NOT USE PLASTIC DRAIN PIPE WITHIN 6" OF VENT CONNECTOR. 3. EXTEND LOW COMBUSTION AIR VENT TO WITHIN 12" OF FLOOR 4. REPAIR INSULATION ON REFRIGERATION LINE 5. PROVIDE SUPPORT ON DUCT WORK ABOVE FLEX CONNECTOR |