Permit: T08CM01054

Parcel: 12710084B


Addresses:

6178 E SPEEDWAY BL


Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01054

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
06/13/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
06/13/2008 ELECTRIC - FINAL Approved
06/12/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TIGHTEN LOOSE FITTINGS AT INSTA-HOT
2. SECURE DISCONNECT TO WALL
3. FINISH #3 & #7 PREVIOUS INSPECTION

*AREA OCCUPIED WITHOUT APPROVAL TO USE
06/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
1. ONLY ONE CONDUCTOR PER TERMINAL LUG
2. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL AND PROPERLY GROUND CIRCUITS
3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS IN PANEL
4. BREAKER LABELING TO BE DISTINGUISHABLE FROM ONE ANOTHER - 408.4
5. TIGHTEN LOOSE FITTINGS
6. SILICONE CANNOT BE USED TO FILL HOLES
7. CLEAN EXCESS DIRT FROM PANEL
8. MAINTAIN WORKING CLEARANCE - 110.26
9. USE PROPER HARDWARE FOR PANEL COVER
10. NEED REVISED PLANS FOR ADDED LOADS AND INSTA-HOT
06/02/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. CONNECT CIRCUITS TO BREAKER
2. FILL UNUSED OPENINGS IN PANEL
3. REVISE CIRCUIT DIRECTORY TO BE AS PER 408.4
4. FINISH BOX MAKE UP & ELECTRIC FOR INSTA-HOTS
5. GROUND EQUIPMENT CONDUCTOR TO BE GREEN OR BARE ENTIRE LENGTH IN RACEWAY
6. BOX OVERFILLED
7. GROUNDING EQUIPMENT & BOND JUMPERS TO BE AS
PER 250.122