Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01054
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/13/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
06/13/2008 | ELECTRIC - FINAL | Approved | ||
06/12/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TIGHTEN LOOSE FITTINGS AT INSTA-HOT 2. SECURE DISCONNECT TO WALL 3. FINISH #3 & #7 PREVIOUS INSPECTION *AREA OCCUPIED WITHOUT APPROVAL TO USE |
|
06/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1. ONLY ONE CONDUCTOR PER TERMINAL LUG 2. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL AND PROPERLY GROUND CIRCUITS 3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS IN PANEL 4. BREAKER LABELING TO BE DISTINGUISHABLE FROM ONE ANOTHER - 408.4 5. TIGHTEN LOOSE FITTINGS 6. SILICONE CANNOT BE USED TO FILL HOLES 7. CLEAN EXCESS DIRT FROM PANEL 8. MAINTAIN WORKING CLEARANCE - 110.26 9. USE PROPER HARDWARE FOR PANEL COVER 10. NEED REVISED PLANS FOR ADDED LOADS AND INSTA-HOT |
|
06/02/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CONNECT CIRCUITS TO BREAKER 2. FILL UNUSED OPENINGS IN PANEL 3. REVISE CIRCUIT DIRECTORY TO BE AS PER 408.4 4. FINISH BOX MAKE UP & ELECTRIC FOR INSTA-HOTS 5. GROUND EQUIPMENT CONDUCTOR TO BE GREEN OR BARE ENTIRE LENGTH IN RACEWAY 6. BOX OVERFILLED 7. GROUNDING EQUIPMENT & BOND JUMPERS TO BE AS PER 250.122 |