Permit: T08CM01054

Parcel: 12710084B


Addresses:

6178 E SPEEDWAY BL


Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM01054

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
06/13/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/13/2008 ELECTRIC - INTERMEDIATE Approved
05/16/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
05/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SUPPORT VDV CABLING IN WALLS 725.24 & 800.24

OK BATHROOMS & STORAGE

DO NOT ROCK LARGE LONG WALL

*725.24 & 3, 800.24 & 3, 300.11 WILL APPLY TO ABOVE CEILING