Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2008 | ELECTRIC - FINAL | Approved | ||
| 10/20/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 10/15/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CLEAN EXCESS FOREIGN MATERIAL FROM DEVICE TERMINALS - PAINT - 110.12 2. NEED ILLUMINATION AT PANEL 110.26(D) 3. LIGHTS NOT INSTALLED AS PER PLANS 4. NO MORE THAN 360 DEG. IN CONDUIT RUNS |
|
| 09/11/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOND POSTING NOT APPLICABLE, THIS IS EXISTING BLDG THAT HAD SERVICE PRIOR TO REMODEL |
|
| 09/10/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BONDING ON SUPPLY SIDE OF SERVICE TO COMPLY WITH 250.102C NEC 2. BOND WATER & GAS PIPING WHERE APPLICABLE 250.104 NEC 3. COMPLETE BONDING & GROUNDING |