Permit: T08CM01037

Parcel: 12703514B


Addresses:

5747 E 5TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/28/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
04/29/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE OBD DAMPERS PER PLANS FOR BOTH PHASES OR PROVIDE A LETTER FROM ENGINEER IF DELETING -- OK FOR CEILING TILES
03/04/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/03/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/08/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILES EAST PHASE I
12/01/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- OK TO SHEETROCK HARD LIDS
- PROVIDE DUCT SMOKE DETECTORS WITH
AUDIBLE & VISIBLE ALARMS
11/04/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL FLEX DUCTS AND HANGER STRAPS PER DETAILS ON PLANS OR HAVE YOUR PLANS REVISED.
2. USE ONLY UL181 DUCT TAPE
3. PROVIDE APPROVED REVISED MECH. PLAN
4. 1/2" DUCT LINER DOES NOT MEET THE MIN. R4.2 INSULATION REQUIREMENT. SEE CITY AMENDMENTS.
5. PROVIDE COPPER CONDENSATE DRAINS AS PER PLANS.