Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/29/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PROVIDE OBD DAMPERS PER PLANS FOR BOTH PHASES OR PROVIDE A LETTER FROM ENGINEER IF DELETING -- OK FOR CEILING TILES |
|
| 03/04/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 03/03/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 01/08/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES EAST PHASE I |
|
| 12/01/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - OK TO SHEETROCK HARD LIDS - PROVIDE DUCT SMOKE DETECTORS WITH AUDIBLE & VISIBLE ALARMS |
|
| 11/04/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL FLEX DUCTS AND HANGER STRAPS PER DETAILS ON PLANS OR HAVE YOUR PLANS REVISED. 2. USE ONLY UL181 DUCT TAPE 3. PROVIDE APPROVED REVISED MECH. PLAN 4. 1/2" DUCT LINER DOES NOT MEET THE MIN. R4.2 INSULATION REQUIREMENT. SEE CITY AMENDMENTS. 5. PROVIDE COPPER CONDENSATE DRAINS AS PER PLANS. |