Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/01/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/28/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED ROOF GFI AND DISCONNECT TIGHTENED UP 2) NEED EXIT AND EM LIGHTS TO WORK FROM PANEL |
|
| 05/13/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FIRST PHASE OK |
|
| 05/12/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO SEE LETTER 2. NEED PLANS REVISED 3. NEED TO SEE EXITS AND EM LIGHTS ON BACK SECTION WORKING |
|
| 01/22/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PHASE ONE OK |
|
| 01/20/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE OBSTRUCTIONS IN FRONT OF PANELS IN ELEC. CLOSET 2. OPEN NEW ELECTRIC EQUIP. AT SERVICE TO NEW PANEL FOR INSPECTION. INSTALL PANEL SCHEDULE. 3. RECALL INSP. HAVE ELECT. CONTR. ON SITE 4. LABEL ALL EQUIP. PANELS, DISC. SW ETC. 5. PROVIDE INSTRUCTIONS FOR INSTALLATION OF LV TRANSFORMERS |