Permit: T08CM01035

Parcel: 129041820

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01035

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/09/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/01/2008 ELECTRIC - FINAL Denied CONTR. REQ. UNSCHED. AFTER HRS. INSP.
PAID $150.00 CK#30192

1. TRACK & CAN LTG. NEEDS TO BE SUPPORTED TO THE STRUCTURE, NOT JUST CEILING GRID, PER 300 NEC REMOVE TILES FOR INSP. CAN LIGHTS TOUCHING WATER LINE
2. REMOVE TRIM TO VIEW MANUF. STICKER
3. PUCK LIGHTS NOT INSTALLED CORRECTLY, INSTALL PER MANUF. OR LISTING OR REMOVE
4. SUPPORT MC CABLE IN GRID PER NEC
5. OK NEW WALL TO COVER IF REMOVAL OF PUCK LIGHTS
6. CEILING FAN NEEDS A FAN RATED BOX ABOVE
04/21/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. EXTERIOR LIGHT MISSING
2. INSTALL ALL DEVICES & COVER PLATES
3. HAVE DEAD RECEPTACLE
4. PANEL DIRECTORY NOT CORRECT/NOT LEGIBLE
5. WALL COVERED WITHOUT INSPECTION TO BE OPEN

PARTIAL INSPECTION, ELECTRICAL CONTRACTOR TO GO THROUGH AND MAKE SURE PER PLAN/CODE