Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01035
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/09/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/01/2008 | ELECTRIC - FINAL | Denied | CONTR. REQ. UNSCHED. AFTER HRS. INSP. PAID $150.00 CK#30192 1. TRACK & CAN LTG. NEEDS TO BE SUPPORTED TO THE STRUCTURE, NOT JUST CEILING GRID, PER 300 NEC REMOVE TILES FOR INSP. CAN LIGHTS TOUCHING WATER LINE 2. REMOVE TRIM TO VIEW MANUF. STICKER 3. PUCK LIGHTS NOT INSTALLED CORRECTLY, INSTALL PER MANUF. OR LISTING OR REMOVE 4. SUPPORT MC CABLE IN GRID PER NEC 5. OK NEW WALL TO COVER IF REMOVAL OF PUCK LIGHTS 6. CEILING FAN NEEDS A FAN RATED BOX ABOVE |
|
04/21/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EXTERIOR LIGHT MISSING 2. INSTALL ALL DEVICES & COVER PLATES 3. HAVE DEAD RECEPTACLE 4. PANEL DIRECTORY NOT CORRECT/NOT LEGIBLE 5. WALL COVERED WITHOUT INSPECTION TO BE OPEN PARTIAL INSPECTION, ELECTRICAL CONTRACTOR TO GO THROUGH AND MAKE SURE PER PLAN/CODE |