Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/20/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND TO CONDENSING UNIT TO BE #10 2. GROUND LUG IN SERVICE PANEL NOT LISTED FOR 2 WIRE TERMINATION 3. EM LIGHT @ REAR OF UNIT TO BE LISTED FOR WET LOCATION 4. EM & EXIT LIGHTS IN EXISTING HOUSE NOT WORKING 5. MISSING EM LIGHT HALLWAY EXISTING HOUSE 6. FEEDER SIZE TO SUB-PANEL NOT PER PLAN |