Permit: T08CM01016

Parcel: 128140630


Addresses:

5232 E 18TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/22/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/20/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND TO CONDENSING UNIT TO BE #10
2. GROUND LUG IN SERVICE PANEL NOT LISTED FOR 2 WIRE TERMINATION
3. EM LIGHT @ REAR OF UNIT TO BE LISTED FOR WET LOCATION
4. EM & EXIT LIGHTS IN EXISTING HOUSE NOT WORKING
5. MISSING EM LIGHT HALLWAY EXISTING HOUSE
6. FEEDER SIZE TO SUB-PANEL NOT PER PLAN