Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01011

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/15/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) RECEIVED CHECK #21060 FOR #150.00
08/14/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) LABEL EQUIPMENT
2) PANEL DIRECTORIES 408.4
3) CLEAN EXCESS PAINT AND FOREIGN MATERIAL FROM DEVICE TERMINALS
4) GFI'S NOT WORKING
5) DO WE NEED GFI IN B101 ?
ROOF:
1) TIGHTEN LOOSE FITTINGS
2) FILL UNUSED OPENINGS IN BOXES
01/05/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE DROP NEEDS TO BE REPLACED WIRES ARE INSULATION AND TAPE ARE COMING APART CAN SEE SPLIT BOLTS AND SERVICE DRIP TO LOW AND NO GROUNDING.