Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM01011
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/15/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
06/26/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SECURELY ATTACH FIXTURES TO GRID 410.16 2) PROPERLY SUPPORT VDV CABLING 725.24 3) SUPPORT WIRES NEEDED FOR ALL EXIT SIGNS 4) JUNCTION BOXES TO BE ACCESSIBLE 5) BOX ABOVE W/H DAMAGED, EXPOSED CONDUCTOR AND BROKEN M/C 6) REMOVE BACK TO 1ST JUNCTION BOX AND CLOSE UNUSED OPENINGS |
|
05/01/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/13/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK HARD LIDS BATHROOMS *VDV CABLING TO BE AS PER 725.24, 800.24, 300.11 |
|
03/27/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS |
|
01/05/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |