Permit: T08CM01009

Parcel: 130060030


Addresses:

1844 S ALVERNON WY


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM01009

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/10/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/05/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH #9 PREVIOUS INSPECTION
07/31/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
07/30/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BOXES MORE THAN 1/4 BOX TO SURFACE 314.20
2) PANEL DIRECTORY TO BE AS PER 408.4 & CORERCT
CIRCUITS
3) GFCI WIRED INCORRECTLY ROOM PRESCHOOL 4
4) HAVE ENGINEER VERIFY ? LIGHTING PRESCHOOL 4 & GFI
5) EXIT LIGHT PRESCHOOL HALL ON SWITCH
6) GFI NOT IN ROOM JANATOR CLOSET
7) LABEL TIME CLOCK & CONTACTOR
8) RECEPTAILS COVERS TO BE PER 406.8
9) USE CORRECT COLOR CONDUIT AT A/C
10) MAINTAIN WORKING CLEARNESS AT A/C DISCONNECTS
110 PROTECT SEAL TITE FROM SHARP METAL EDGES
12) SEAL UNUSED CONDUIT OPENNES UNIT APPROVED SEALS
07/29/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*