Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM01009
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/10/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/05/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH #9 PREVIOUS INSPECTION |
|
07/31/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
07/30/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOXES MORE THAN 1/4 BOX TO SURFACE 314.20 2) PANEL DIRECTORY TO BE AS PER 408.4 & CORERCT CIRCUITS 3) GFCI WIRED INCORRECTLY ROOM PRESCHOOL 4 4) HAVE ENGINEER VERIFY ? LIGHTING PRESCHOOL 4 & GFI 5) EXIT LIGHT PRESCHOOL HALL ON SWITCH 6) GFI NOT IN ROOM JANATOR CLOSET 7) LABEL TIME CLOCK & CONTACTOR 8) RECEPTAILS COVERS TO BE PER 406.8 9) USE CORRECT COLOR CONDUIT AT A/C 10) MAINTAIN WORKING CLEARNESS AT A/C DISCONNECTS 110 PROTECT SEAL TITE FROM SHARP METAL EDGES 12) SEAL UNUSED CONDUIT OPENNES UNIT APPROVED SEALS |
|
07/29/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |