Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T08CM01005
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
08/20/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANCELLED PER SHAWN |
|
08/19/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) A/C CIRCUIT #6 AL SE CABLE RATED FOR 4 AMPS IN 60" TABLE. 40 AMP BREAKER AND FUSE MAXIMUM FOR RANGE, 1-A/C CIRCUIT 2) NUMBER A/C UNITS AT PANEL 3) REMOVE WHIP CONNECTOR FOR GAS DRYER 4) OPEN GROUND IN BEDROOM OUTLET AT TOP OF STAIRS 5) NO LADDER TO INSPECT ATTIC |