Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T08CM01004
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
08/20/2008 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER SHAWN |
|
08/19/2008 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED DBL CROSS BRACING AT GABLE ENDS 2) A/C CIRCUIT #6 AL. GOOD FOR 40 AMPS AT 60 DEGREE MIN. CIRCUIT AMPS 33.5 USE 40 AMP BREAKER 35 AMP MIN. FUSE 3) REMOVE GAS FLEX |