Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T08CM00994

Parcel: 136048210

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM00994

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/22/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/16/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. STRAP SER CABLE THROUGH ATTIC SPACE MAX EVERY 54"
2. LOW VOLTAGE AND HIGH VOLTAGE CANNOT BE IN SAME JUNCTION BOX FOR DOORBELL SYSTEM
3. SERVICE NOT PER PLAN NEED APPROVED REVISION TO PLANS
4. INSTALL CONNECTORS ON SER CABLE AT SERVICE EQUIPMENT