Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T08CM00990
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/08/2008 | EXT METAL CLIPS/EXT SHEATHING | Approved | ||
05/30/2008 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) H.D. AT HALLWAY-WILL CHECK AT INTERMEDIATE INSPECTION 2) OK TO COVER |
|
05/27/2008 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 1ST AND 2ND BEDROOMS SOUTH OF GARAGE REQUIRES 2-2 X 8 HEADER AND MASTER 2) HEADERS LIVING AND KITCHEN TO BE DBL 2 X 6 3) DBL ? HEADS REQUIRED AT FRONT ENTRY HALLWAY TO KIT, FRONT WINDOW 4) DBL HTT16 NOT INSTALLED PER PLAN AT GARAGE FRONT 5) NEED REVISION FOR SHEARWALLS IN HALLWAY 6) 16" HIGH HTT16 REQUIRED AT SHEARWALL GARAGE TO HOUSE HTT22 INSTALLED CONDENSATE CAN'T DRAIN HTT IN THE WAY |