Permit: T08CM00978

Parcel: 11306147B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T08CM00978

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/15/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
05/14/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. INDIRECT WASTE PIPING TO BE APPROVED MATERIAL INSTALLED PER 2006 UPC
2. ALL INDIRECT WASTE PIPING TO HAVE A
MINIMUM 1" AIR GAP
3. WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN, IT SHALL HAVE ITS INVERT TAKEN OFF ABOVE THE DRAINAGE CENTER LINE, DOWNSTREAM OF THE TRAP BEING SERVED
4. VENT CONNECTION TO BE THROUGH A WYE
BRANCH FITTING
5. THE WATER HEATER SHALL NOT BE THE SOLE SOURCE OF HEAT CONTROL AT PUBLIC USE LAVATORIES.