Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/15/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 05/14/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. INDIRECT WASTE PIPING TO BE APPROVED MATERIAL INSTALLED PER 2006 UPC 2. ALL INDIRECT WASTE PIPING TO HAVE A MINIMUM 1" AIR GAP 3. WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN, IT SHALL HAVE ITS INVERT TAKEN OFF ABOVE THE DRAINAGE CENTER LINE, DOWNSTREAM OF THE TRAP BEING SERVED 4. VENT CONNECTION TO BE THROUGH A WYE BRANCH FITTING 5. THE WATER HEATER SHALL NOT BE THE SOLE SOURCE OF HEAT CONTROL AT PUBLIC USE LAVATORIES. |