Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T08CM00978
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/06/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* REVISED APPROVED PLAN ON SITE, TEST ON VENT THRU ROOF GREASE TRAP AREA OK |
|
05/05/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE SINK TRAP VENT AND TEST ON REVENT FOR THIS AREA |
|
05/02/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - WATER TEST DWV THRU ROOF FOR HAND SINK & FLOOR SINK OK - WATER PIPING THIS AREA OK - CAPS ON UNDER SLAB OK - PIPE WRAPS THIS AREA OK 1. PROVIDE CORRECT INSTALL OF GREASE TRAP WITH TEST TO REVENT AND CORRECT VENT FOR FLOW CONTROL THIS IS TO BE ON REVISED APPROVED PLAN. |
|
05/01/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. NOT INSTALLED PER PLAN NO REDLINES ON SITE SHOWING P.O.C TO EXISTING 2. GREASE TRAP REPLACED AND COVERED W/O INSPECTION NO FLOW CONTROL VENT MAY BE NO SYSTEM VENT BETWEEN FLOW CONTROL AND G.T EXPOSE ALL NEW WORK 3. FEMALE ABS THREADS MAY NOT BE IN UNACCESSIBLE LOCATION 4. PLUMBERS TAPE NOT APPROVED STRAP 5. UNDERGROUND COPPER TO BE TYPE "K" 6. JIM CAPS NOT APPROVED FOR PERMANENT CAPPING |