Permit: T08CM00978

Parcel: 11306147B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM00978

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/06/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
REVISED APPROVED PLAN ON SITE, TEST ON VENT THRU ROOF GREASE TRAP AREA OK
05/05/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROVIDE SINK TRAP VENT AND TEST ON
REVENT FOR THIS AREA
05/02/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- WATER TEST DWV THRU ROOF FOR
HAND SINK & FLOOR SINK OK
- WATER PIPING THIS AREA OK
- CAPS ON UNDER SLAB OK
- PIPE WRAPS THIS AREA OK

1. PROVIDE CORRECT INSTALL OF GREASE TRAP WITH TEST TO REVENT AND CORRECT VENT FOR FLOW CONTROL
THIS IS TO BE ON REVISED APPROVED PLAN.
05/01/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. NOT INSTALLED PER PLAN NO REDLINES ON SITE
SHOWING P.O.C TO EXISTING
2. GREASE TRAP REPLACED AND COVERED W/O INSPECTION
NO FLOW CONTROL VENT
MAY BE NO SYSTEM VENT BETWEEN FLOW CONTROL AND G.T
EXPOSE ALL NEW WORK
3. FEMALE ABS THREADS MAY NOT BE IN UNACCESSIBLE LOCATION
4. PLUMBERS TAPE NOT APPROVED STRAP
5. UNDERGROUND COPPER TO BE TYPE "K"
6. JIM CAPS NOT APPROVED FOR PERMANENT CAPPING