Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00978
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/19/2008 | ELECTRIC - FINAL | Approved | ||
05/16/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PANEL DIRECTORY NOT CORRECT 2. CHECK WIRING/MAKE UP TO SANDWICH COUNTER AND PREP TABLE - NOT WIRED PER PLAN, MAKE SURE ALL CIRCUITING PER PLAN 3. LIGHTING NOT PER PLAN/BULBS NOT IN |
|
05/15/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ON ROOF 1. SEAL FLASHINGS 2. SQUARE UP FITTINGS/LB's SECURE EMT INTERIOR NOT READY FOR FINAL INSPECTION |
|
05/12/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY FOR SERVICE & ROOF 1. EXISTING SERVICE CONDUCTORS NOT RATED FOR 200 AMP 2. IDENTIFY "SERVICE DISCONNECT" AS SUCH 3. DEMO OLD FEEDERS 4. FEEDER EQUIPMENT GROUND UNDERSIZED 5. FEEDER L.B NOT SQUARE INTO RACEWAY 6. TIGHTEN ALL FITTINGS AND STRAPS FOR FEEDER RACEWAY, STAY MINIMUM 36" IN FRONT OF ROOF PANEL, SECURE ALL EMT TO SURFACE, NOT JUST ON BLOCKS, SEAL FLASHING 7. ENCLOSURES FOR WALK IN CONDENSORS TO BE OPEN FOR INSPECTION - MISSING K.O IN GFI J-BOX |
|
05/08/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |