Permit: T08CM00978

Parcel: 11306147B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00978

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/19/2008 ELECTRIC - FINAL Approved
05/16/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PANEL DIRECTORY NOT CORRECT
2. CHECK WIRING/MAKE UP TO SANDWICH COUNTER AND PREP TABLE - NOT WIRED PER PLAN, MAKE SURE ALL CIRCUITING PER PLAN
3. LIGHTING NOT PER PLAN/BULBS NOT IN
05/15/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ON ROOF
1. SEAL FLASHINGS
2. SQUARE UP FITTINGS/LB's SECURE EMT

INTERIOR NOT READY FOR FINAL INSPECTION
05/12/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY FOR SERVICE & ROOF
1. EXISTING SERVICE CONDUCTORS NOT RATED FOR 200 AMP
2. IDENTIFY "SERVICE DISCONNECT" AS SUCH
3. DEMO OLD FEEDERS
4. FEEDER EQUIPMENT GROUND UNDERSIZED
5. FEEDER L.B NOT SQUARE INTO RACEWAY
6. TIGHTEN ALL FITTINGS AND STRAPS FOR FEEDER RACEWAY, STAY MINIMUM 36" IN FRONT OF ROOF PANEL, SECURE ALL EMT TO SURFACE, NOT JUST ON BLOCKS, SEAL FLASHING
7. ENCLOSURES FOR WALK IN CONDENSORS TO BE OPEN FOR INSPECTION - MISSING K.O IN GFI J-BOX
05/08/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*