Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL & HARD LID COVER |
|
| 04/28/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IDENTIFY WHITE USED AS HOT - NEC 200.7 C2 2. J-NAILS FOR EMT - NOT MC, USE MC STRAPS - NEC 110.3B 3. MISSING NAIL PLATES FOR MC - NEC 330.17 4. EMT TO BE SECURED WITHIN 3' OF ENCLOSURES AND MAX 10' INTERVALS - NEC 358.30A 5. EQUIPMENT GROUNDING CONDUCTOR TO WRAP MINIMUM 2/3RDS AROUND GROUND SCREW WITH NO INSULATION UNDER SCREW - NEC 110.3B, 250.4 6. MISSING MUD RINGS - NEC 314.20 7. HAVE OVERFILLED J-BOXES -- NEC 314.16 8. HAVE OVERFILLED WIRE NUTS -- NEC 110.3B 9. MC TO BE SECURED WITHIN 12" OF TERMINATIONS AND MAX 6' INTERVALS -- NEC 330.30B |