Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/24/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL & HARD LID COVER
04/28/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IDENTIFY WHITE USED AS HOT - NEC 200.7 C2
2. J-NAILS FOR EMT - NOT MC, USE MC STRAPS - NEC 110.3B
3. MISSING NAIL PLATES FOR MC - NEC 330.17
4. EMT TO BE SECURED WITHIN 3' OF ENCLOSURES AND
MAX 10' INTERVALS - NEC 358.30A
5. EQUIPMENT GROUNDING CONDUCTOR TO WRAP
MINIMUM 2/3RDS AROUND GROUND SCREW WITH NO INSULATION UNDER SCREW - NEC 110.3B, 250.4
6. MISSING MUD RINGS - NEC 314.20
7. HAVE OVERFILLED J-BOXES -- NEC 314.16
8. HAVE OVERFILLED WIRE NUTS -- NEC 110.3B
9. MC TO BE SECURED WITHIN 12" OF TERMINATIONS AND
MAX 6' INTERVALS -- NEC 330.30B