Permit: T08CM00948

Parcel: 13312006J

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
08/04/2008 MECHANICAL - HOODS Approved IVRS - Inspection :*
FOR FINAL PROVIDE AIR BALANCE REPORT
CAPTURE & CONTAINMENT TEST, HEAT SENSOR TEST
08/01/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
2ND LAYER OF FIRE WRAP OK
OK TO INSTALL HOOD
07/31/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
OK FOR 2ND LAYER OF FIRE WRAP
07/30/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
CHECKED WELDS ON GREASE DUCT
OK FOR 1ST LAYER OF FIRE WRAP
06/13/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
DISCUSSED INSTALLATION