Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2009 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
| 04/30/2009 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) PLAN CALLS FOR 1" H20 LINE, 1" LINE FOR ADDITION IS TIED INTO EXISTING 3/4" DIAMETER HOUSE LINE, MAIN LINE CAN'T BE SMALLER THAN NEW LINE 2) LEAK AT TIE IN JOINT OK TO COVER ALL EXCEPT TIE IN |
|
| 04/28/2009 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) NOTE: DON'T COVER SEWER UNTIL CONNECTED TO HCS, MAINTAIN 1/4" PER FT. SLOPE, INSTALL TRACER WIRE |