Permit: T08CM00930

Parcel: 11016223A

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM00930

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/22/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
09/19/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/12/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PLANS REQUIRE COPPER INSULATED CONDENSATE DRAINS
2. STEP UP TO 1" AT TEE
3. DETAIL ON PLANS REQUIRE METAL DRAW BANDS ON
FLEX DUCTS.
4. HAVE PLANS REVISED IF YOU DON'T WANT TO FOLLOW DETAILS.