Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES |
|
| 09/19/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 09/12/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PLANS REQUIRE COPPER INSULATED CONDENSATE DRAINS 2. STEP UP TO 1" AT TEE 3. DETAIL ON PLANS REQUIRE METAL DRAW BANDS ON FLEX DUCTS. 4. HAVE PLANS REVISED IF YOU DON'T WANT TO FOLLOW DETAILS. |