Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T08CM00930
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
09/15/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. OK METER SECTION 2. INSTALL PROTECTIVE BUSHING ON CLOSE NIPPLE IN GUTTER SIDE 3. INSTALL MAIN BONDING JUMPER DISCONNECT 4. NEED TO POST BOND FOR POWER 5. RECALL AFTER PANEL GUT INSTALED |
|
09/12/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. INSTALLATION BY ELECTRICAL CONTRACTOR OK ABOVE CEILING 2. NEED TO INSTALL TELEPHONE & DATA CABLING. RECALL FOR CEILING INSPECTION AFTER THIS IS COMPLETE. 3. INSTALL MAIN BONDING JUMPER IN SERVICE DISCONNECT. PLEASE EXPLAIN GROUNDING AT SERVICE. 4. PLAN SHOWS LOAD OF 135 AMPS ON 100 AMP SERVICE PLEASE EXPLAIN 5. MARK "SERVICE DISCONNECTS" - "1 OF 3", "2 OF 3", "3 OF 3" |