Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* ALL CORRECTIONS HAVE BEEN MADE |
|
| 06/19/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* AIR BALANCE PER M-2 SPEC. 10 AFTER BUILDING IS OCCUPIED PROVIDE CLEANOUTS IN CONDENSATE PIPE PER PLANS CONDENSATE PIPING NOT INSULATED CONDENSATE TAILPIECE INCORRECT SIZE CONDENSATE P-TRAP VENTS INSTALLED INCORRECTLY SEE BUILDING INSPECTOR FOR TEMP C OF O |