Permit: T08CM00926

Parcel: 13824093E


Addresses:

1601 W COMMERCE CT


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM00926

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/17/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
06/12/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RETURN AIR BOOTS NOT PER PLANS
2. FLEX NOT SUPPORTED PER PLANS
3. INSULATION NOT COMPLETE
4. CONDENSATE PIPING NOT COMPLETE, MUST BE INSTALLED PER PLANS
5. FLEX CONNECTIONS AT SUPPLY AND RETURN DUCTS NOT INSTALLED PER PLANS

REFEE WILL APPLY TO NEXT INSPECTION

FLUE PIPING IN WAREHOUSE NOT PER CODE, NO FINAL UNTIL CORRECTED.
06/10/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
INSTALL PER NOTES & DETAILS ON PLANS
06/02/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*