Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T08CM00923
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/26/2008 | FRAMING | Approved | IVRS - Inspection :* | |
06/24/2008 | FRAMING | Partial Approval | 1) EXPOSED GREEN PLATE AT REAR PORCH 2) NEED LPI BOOK, FOR HOLE DISTANCES REQUIRED-DRILLING MAX/MIN 3) TRAP ON WASHER TO HIGH SEE FLOOR AT WASHER 4) PLANS CALL FOR 50 AMP CIRCUIT RANGE #6 AL. AT 60 DEGREE=40 AMPS ONLY 5) SECURE PEX TOILET 1ST FLOOR 6) 2ND FLOOR TUB NOT INSTALLED, ACCES HOLE OUTSIDE HALL RECEPT TO FAR AWAY 7) TUB VENT 2 X 4 OVER DRILLED ADD FHA STRAPS 8) MOVE S/DET. AWAY FROM DUCT WEST BEDROOM 2ND FLOOR REAR 9) ROMEX AT ROOF PENETRATION, AGAINST SIDE OF SHARP CONDUIT 10) BRIAN, IS THERE A MODEL LIKE THIS HOUSE FINISH, WOULD LIKE TO LOOK AT STAIR 11) HEAT PUMP CIRCUIT #6 WIRE BREAKER SIZE NOT GIVEN ? |