Inspection History: FRAMING

Permit Number - T08CM00923

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
06/26/2008 FRAMING Approved IVRS - Inspection :*
06/24/2008 FRAMING Partial Approval 1) EXPOSED GREEN PLATE AT REAR PORCH
2) NEED LPI BOOK, FOR HOLE DISTANCES REQUIRED-DRILLING MAX/MIN
3) TRAP ON WASHER TO HIGH SEE FLOOR AT WASHER
4) PLANS CALL FOR 50 AMP CIRCUIT RANGE #6 AL. AT 60 DEGREE=40 AMPS ONLY
5) SECURE PEX TOILET 1ST FLOOR
6) 2ND FLOOR TUB NOT INSTALLED, ACCES HOLE OUTSIDE HALL RECEPT TO FAR AWAY
7) TUB VENT 2 X 4 OVER DRILLED ADD FHA STRAPS
8) MOVE S/DET. AWAY FROM DUCT WEST BEDROOM 2ND FLOOR REAR
9) ROMEX AT ROOF PENETRATION, AGAINST SIDE OF SHARP CONDUIT
10) BRIAN, IS THERE A MODEL LIKE THIS HOUSE FINISH, WOULD LIKE TO LOOK AT STAIR
11) HEAT PUMP CIRCUIT #6 WIRE BREAKER SIZE NOT GIVEN ?