Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T08CM00917
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2009 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
04/03/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) NO BOND REQUIRED 2) CALL FOR FINALS AFTER POWER CHECK 3) BOLTS FOR HAND HOLES MISSING |
|
03/31/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. BOND JUMPERS ON SUPPLY SIDE OF SERVICE NEED TO BE SIZED PER 250-102 C 1/0 CU 2. BOND BUSHINGS OR BOND LOCKNUTS PER NEC 250.92 3. NEUTRAL BOND IN X-FORMER PER 250.66 - #4 C.U. |
|
10/21/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK GROUND RODS - SERVICE & POLES OK 1 1/2" PVC FOR IRRIGATION CONTROLS |
|
09/22/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK LAST (6) POLE BASES AS MARKED ON PLANS |
|
09/04/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK POLE BASES AND PVC AS MARKED |
|
08/26/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 7 POLE BASES AS MARKED |
|
08/20/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK AS MARKED ON PLANS OK 7 POLE BASES |
|
08/12/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK AS MARKED |
|
08/04/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK AS MARKED ON PLANS |
|
08/01/2008 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
07/22/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK AS MARKED ON PLANS |
|
07/14/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK AS MARKED ON PLANS |
|
07/11/2008 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* CANCELED |