Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T08CM00914
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
09/19/2008 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* EXISTING BLD. NO BOND REQUIRED |
|
09/18/2008 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
09/17/2008 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. BOND 200A SERVICE DISC. SW 2. SIZE SUPPLY SIDE BOND JUMPER PER 250.66 NEC 3. INSTALL FUSES, R-PINS |