Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM00914
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/02/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/26/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CORRECTIONS FOR INSPECTION ON 2/26/09 2) CALL WHEN COMPLETE |
|
02/26/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. USE OR INSTALL HANDLE TIES FOR MULTI-CIRCUIT MODULAR FURNITURE - CLEARANCE ABOVE PANELS IN ELECTRIC ROOM PER 110.26 605 NEC |
|
02/18/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK CEILING 2ND FLOOR T.I. SHELL OK TCO 2. OK TO USE MOLDED CORDS FOR LIFT STATION PUMPS, PUMPS ARE UL LISTED |
|
02/17/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
02/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ELEC. CONTR. TO RELOCATE DISC. SWITCHES FOR AC UNITS ON ROOF AS DISCUSSED TO TRY TO MEET CLEARANCE REQUIREMENTS |
|
02/06/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
02/04/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NEED TO LOOK AT TEMPORARY POWER |
|
01/30/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CONSTRUCTION PERSONAL TO USE GFI PROTECTED RECEPTS ONLY 2) CONTR. RESPONSIBLE FOR ONLY AUTHORIZED PERSONS TO ACCESS ELECTRIC EQUIPMENT 3) EXISTING BLDG SERVICE INCR, NO BOND REQUIRED 4) OK TO ENERGIZE A & A2 AND B |
|
01/21/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK REMAINDER OF BASEMENT ROUGH 2. OK PONY WALLS OFFICES |
|
01/06/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PANEL "B" MAKE UP |
|
12/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK BASEMENT ELEVATOR #104 AREA AND EJECTION PIT ROOM WALLS, UPPER AND LOWER LOBBY HARD LIDS #102, #104, #200 |
|
12/10/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS BASEMENT NEW ADDITION |
|
12/02/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. TENANT 2ND FLOOR SPACE WALLS OK 2. STAIRWAY NEED TO BE FINISHED |
|
11/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK BASEMENT HARD LID, NEW ADDITION |
|
09/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK EXISTING AREA SOUTH OFFICE UNDERSLAB BRANCH CIRCUITS |