Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/21/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* MC CABLE TO BE SUPPORTED TO STRUCTURE OR PER 330.30 AND 330.11 2B, SUPPORT PULL BOX FOR PANEL FEEDER |
|
| 01/07/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. FINISH VDV CABLING PER 725.24, 760.24, 800.24, 300.11 OK TILE GRID LINE E EXCEPT AS NOTED |