Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM00913
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/23/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1. OK WALLS RECEPTION AREA - PHASE TWO 2. OK HARD LIDS |
|
12/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PHASE ONE |
|
12/02/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NO MORE THAN 360 DEG. IN A CONDUIT RUN 2. PROTECT PVC AT BASE PLATES 3. SUPPORT CONDUITS IN WALLS PVC AND EMT 4. M/C CABLE NOT TO BE SUPPORTED OFF OF OTHER WIRING METHODS 5. EXPOSED CONDUCTORS IN COMBUSTIBLES 6. SUPPORT OR REMOVE OLD VDV CABLING 725.3 &24, 800.3 & 24 7. FLASH BOXES TO BE PER 517.13 AND CONTINUOUS 8. RECOVERY ROOMS MAY NEED TO BE AS PER 517.13 HAVE ENGINEER VERIFY 9. PROTECT MC CABLE AT SHALLOW STUDS 10. INSTALL ALL "P" RINGS |