Permit: T08CM00904

Parcel: 12217365A

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
12/15/2008 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
OK FOR SHEETROCK
12/12/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE A BUSHING AT REFER LINE PENETRATION INTO CABINET.
2. DO NOT USE PVC IN A RETURN PLENUM
3. CPVC IS OK
4. PROVIDE OVERFLOW SENSORS
5. PROVIDE BACKING AT SIDE WALL REGISTER BOXES PRIOR TO SHEETROCK
6. PROVIDE NAIL PLATES @ CONDENSATE PIPE IN WALL
7. R8 DUCT INSULATION REQUIRED IN ATTIC ABOVE ATTIC INSULATION
8. SEE IECC AND CITY AMENDMENTS