Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* OK FOR SHEETROCK |
|
| 12/12/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE A BUSHING AT REFER LINE PENETRATION INTO CABINET. 2. DO NOT USE PVC IN A RETURN PLENUM 3. CPVC IS OK 4. PROVIDE OVERFLOW SENSORS 5. PROVIDE BACKING AT SIDE WALL REGISTER BOXES PRIOR TO SHEETROCK 6. PROVIDE NAIL PLATES @ CONDENSATE PIPE IN WALL 7. R8 DUCT INSULATION REQUIRED IN ATTIC ABOVE ATTIC INSULATION 8. SEE IECC AND CITY AMENDMENTS |