Permit: T08CM00904

Parcel: 12217365A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/30/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL ELECTRIC
03/27/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED CONNECTOR AT HOOD
2. LOOSE FITTINGS FOR WATER HEATER
3. PROPERLY GROUND FIXTURES
4. USE APPROVED BOXES FOR M/C CABLE AND GROUND BOX
5. USE APPROVED HARDWARE
6. CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANEL
7. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL
8. #8 NM CABLE BREAKER AMPACITY TO BE AS PER 334.80
9. A/C DISCONNECTING MEANS TO BE WITHIN SITE-EAST
03/25/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ARC FAULTS NOT WORKING, CONTR. TO POWER CHECK PRIOR TO CALLING IN FINAL INSP.
2. GFI BEHIND STOVE IN UNIT #1102
3. STOPPED INSP. AT BOTTOM FLOOR