Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T08CM00902

Parcel: 112062320


Addresses:

2520 N CAMPBELL AV


Inspection Status: Denied

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM00902

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Denied

Date Description Inspector Results Comments
11/20/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NO PLANS ON SITE
2. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANELS
3. STRAP CONDUIT AS PER CODE
4. TIGHTEN LOOSE FITTINGS
5. WHERE ARE CONDUCTORS FOR EXIT LIGHTS

*A REFEE PER ADMIN. CODE MAY BE ASSESSED
11/13/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
There is no plan or job inspection card on site.| 925*
NO ELECTRICAL PLANS OR NOTES