Permit: T08CM00879

Parcel: 141351690

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T08CM00879

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
05/30/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
05/29/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/28/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SPECIAL INSPECTION REPORT ON ENGINEERING FIX FOR HOLDOWNS AT FRONT OF GARAGE
2) NAILS NEEDED IN HOLDOWNS WEST OF GARAGE DOOR
3) FIX PAPER AT LANDING AT BOTTOM OF STAIRS EXTERIOR WALL
4) YARD WATER LINE STILL LEAKING AT HOUSE EXTERIOR
05/27/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED ENGINEERING FOR STEMWALL FIX
05/22/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GARAGE STEMWALL HOLDOWNS TO ENGINEER FIX
2) SHEAR PLAN CALLS FOR HTT16, KB11 7" MIN EMBEDEMNT AT1 GARAGE/HOUSE
3) SHIM TRIMMER UNDER BEAM TOP PLATE EAST WALL
4) 2-2 X 6 POST UNDER HEADER AT BOTTOM OF STAIRWAY
5) 4-2 X 4 POST AT LVL HEADER ADJACENT TO STAIRS
6) 5-1/8 X 12 GLUE LAMB CENTER OF FIRST FLOOR
7) NAIL PROTECT WATER LINES TOP PLATE GARAGE EAST WALL
8) LEAK AT WATER LINE SERVICE AT HOUSE
9) NAIL PROTECT 1 1/2" VENT LINE MASTER CLOSET
04/22/2008 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
- BOLTS AND HOLD DOWNS THROUGHOUT
- SHIM TRIMMER EAST SIDE GARAGE UNDER BEAM
- ADD TRIMMER UNDER BEAM ABOVE BOTTOM OF
STAIRS EAST WALL