Permit: T08CM00860

Parcel: 131080210


Addresses:

6041 E 23RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/25/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/19/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ROMEX TO BE STAPLED WITHIN 12" OF BOXES
8" FOR SINGLE BOX
2. CANNOT RUN SINGLE CONDUCTOR EXPOSED
3. NEED MIN. 6" OF FREE CONDUCTOR LENGTH IN BOXES
4. ROMEX LESS THAN 8' DOWN TO BE PROTECTED FROM PHYSICAL DAMAGE
5. STRAP EMT WITHIN 3' OF BOXES
6. SEAL OPEN BREAKER POSITION IN PANEL
7. NEED PANEL DIRECTORY
8. PROPERLY SECURE PANEL TO WALL
9. CANNOT HAVE 14 GAUGE WIRE ON 20 AMP CIRCUIT
10. PVC TO BE MIN. 18" DEEP