Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00858
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2008 | ELECTRIC - FINAL | Approved | DELTA 2 REVISION DELETED BACKUP GENERATOR. APPROVED PER LAST COMMENT BY RICH JIROUDEK. | |
08/20/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. HAVE ENGINEER CHECK NUMBERS (LOAD CALCULATIONS) FOR ATLAS COMPRESSOR 40 HP MTR DRAWS 112 AMPS @ 208V PLAN SHOWS 9600 WATTS OF LOAD PER PHASE. CHECK LARGEST MOTOR LOAD FOR SERVICE CALCULATION 2. REVISED PLANS NEED TO GO THROUGH PLAN REVIEW FOR APPROVED |
|
08/13/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PREVIOUS INSPECTION ITEMS CORRECTED 2. NEED TO HAVE APPROVED PLANS ON SITE 3. NEED REVISION TO PLANS FOR CHANGES TO AIR COMPRESSOR 4. NEED GROUNDING ELECTRODE SYSTEM FOR 45KVA SYSTEM |
|
08/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ONE EM LIGHT NOT OPERATIONAL 2. PROPERLY MOUNT RECEPTACLES INDUSTRIAL COVERS 3. NEED PROTECTIVE BUSHINGS ON CONNECTORS WITH #4 OR LARGER 4. BOND ARC LINES WITH #6 5. CHECK WITH BUILDING INSPECTOR FOR TCO |
|
07/29/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |