Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM00839
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/17/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/16/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ALL 15a & 20a 120V RECEPTS TO BE GFI PROTECTED IN KITCHEN 2. BLANK MISSING SWITCH IN PLATE |
|
07/15/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TOO MANY RECESSED FIXTURES ON ONE CIRCUIT 2. MISSING RECEPT BAR AREA 3. HAVE RECEPTS WITH NO POWER 4. LIGHT FIXTURES IN KITCHEN TO BE ATTACHED TO GRID 5. ALL 15A & 20A RECEPT IN COMMERCIAL KITCHEN TO BE GFI PROTECTED 6. VERIFY DIMMERS SIZED PROPERLY 7. STRAP SEAL TIGHT ABOVE WALK IN COOLERS 8. SEAL RACEWAYS INTO WALK IN COOLERS 9. PROVIDE DISCONNECTING MEANS FOR APPLIANCES PER PLAN 10. WHAT ARE TOGGLE SWITCHES & DISCONNECT ABOVE CEILING IN KITCHEN FOR? 11. MISSING PLATE ON RECEPT OFFICE 12. SECURE RECEPT TO WALL OFFICE 13. SOME EM LIGHTS NOT WORKING 14. MISSING EM LIGHT 15. MISSING LIGHT & EM LIGHT FIRE RISER ROOM 16. NEED WEATHERPROOF ENCLOSURES FOR WALK IN CONDENSING UNITS 17. OVERFUSING ON ICE MACHINE CONDENSING UNIT 18. HAVE ELECTRICAL CONTRACTOR GO THROUGH ENTIRE JOB AND INSTALL PER PLANS AND NEC 19. MISSING LIGHTS IN RESTROOMS |