Permit: T08CM00839

Parcel: 141177160

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00839

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/17/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/16/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. ALL 15a & 20a 120V RECEPTS TO BE GFI PROTECTED IN KITCHEN
2. BLANK MISSING SWITCH IN PLATE
07/15/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TOO MANY RECESSED FIXTURES ON ONE CIRCUIT
2. MISSING RECEPT BAR AREA
3. HAVE RECEPTS WITH NO POWER
4. LIGHT FIXTURES IN KITCHEN TO BE ATTACHED TO GRID
5. ALL 15A & 20A RECEPT IN COMMERCIAL KITCHEN TO BE GFI PROTECTED
6. VERIFY DIMMERS SIZED PROPERLY
7. STRAP SEAL TIGHT ABOVE WALK IN COOLERS
8. SEAL RACEWAYS INTO WALK IN COOLERS
9. PROVIDE DISCONNECTING MEANS FOR APPLIANCES
PER PLAN
10. WHAT ARE TOGGLE SWITCHES & DISCONNECT ABOVE CEILING IN KITCHEN FOR?
11. MISSING PLATE ON RECEPT OFFICE
12. SECURE RECEPT TO WALL OFFICE
13. SOME EM LIGHTS NOT WORKING
14. MISSING EM LIGHT
15. MISSING LIGHT & EM LIGHT FIRE RISER ROOM
16. NEED WEATHERPROOF ENCLOSURES FOR WALK IN CONDENSING UNITS
17. OVERFUSING ON ICE MACHINE CONDENSING UNIT
18. HAVE ELECTRICAL CONTRACTOR GO THROUGH ENTIRE JOB AND INSTALL PER PLANS AND NEC
19. MISSING LIGHTS IN RESTROOMS