Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM00839
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/16/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS & SOFFITS |
|
05/27/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROTECT MC CABLES AT SHALLOW STUDS 2. SUPPORT VDV CABLING IN WALLS 725.24, 800.24 3. MAINTAIN FIREWALL SEPARATION 4. PLAN DOES NOT ALLOW DIE CAST FITTINGS 5. SUPPORT M/C WITHIN 12" OF CANS & BOXES 6. OK OUTSIDE INTERIOR ONLY WALLS |