Permit: T08CM00837

Parcel: 13423424B


Addresses:

251 S WILMOT RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM00837

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/31/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL
2) LEFT GAS CARD
3) WILL CHECK AIR BALANCE ON POOL HEATER INSPECTION
08/28/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PAINT ALL EXPOSED PVC WITH LATEX PAINT
2) SUPPORT EVERY 4'
3) SECURE MINI SPLIT CONDENSOR
4) DO NOT USE DUCT TAPE OUTDOORS
5) PROVIDE MINIMUM 1/8" PER FT. SLOPE ON CONDENSATE DRAINS ON ROOF
6) EF10 & EF11 NOT BALANCED PER SPECS
7) GET DIRECTION FROM ENGINEER
08/25/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) LABEL ALL FIRE DAMPERS ACCESS DOORS AND PANELS PER CODE
2) FINISH VENT CONNECTION TO WATER HEATER
3) FINISH EXHAUST FAN INSTALLATION AND REPAIR INSULATION IN ELECTRIC ROOM
4) GUEST LAUNDRY DRYER VENT CRIMPED END BACKWARDS
5) PROVIDE INSTALL INSTRUCTIONS FOR POOL HEATER AND VENT KIT
6) NEED TO SEE ROOF TOP EQUIPMENT
7) PROVIDE AIR BALANCE
07/30/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
OK FOR FINAL LIVING UNITS ONLY
07/27/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) FIRE SMOKE DAMPERS ACTUATION 100 PERCENT CLOSURE OK X9