Permit: T08CM00837

Parcel: 13423424B


Addresses:

251 S WILMOT RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM00837

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/31/2009 MECHANICAL - ABOVE CEILING Approved
07/29/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PARTIAL
OK FOR CEILING TILES
07/21/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) MINI SPLIT CONDENSATE TERMINATE RUBBER HOSE WITH A FITTING
2) SUPPORT ALL FLEX DUCT OFF OF GRID
3) SUPPORT CEILING DIFFUSERS
4) TERMINATE SECONDARY DRAINS TO A CONSPICIOUS LOCATION OR PROVIDE AN OVER FLOW SENSOR
05/21/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FLOOR SINKS NOT ALLOWED IN RETURN AIR PLENIUM AS PER MECHANICAL AND PLUMBING CODES
2) COMBUSTIBLES NOT ALLOWED IN A RETURN PLENIUM
3) CHECKED FIRE DAMPERS IN SHAFTS
4) SEAL ALL PENETRATIONS IN SHAFTS
05/06/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/26/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/18/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/17/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/16/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/28/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*