Permit: T08CM00837

Parcel: 13423424B


Addresses:

251 S WILMOT RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T08CM00837

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/15/2009 PLUMBING - FINAL Approved
09/14/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) MAKE TUB AND SHOWER ENCLOSURE WATER TIGHT UNITS #109 & 136
2) PROVIDE PROOF OF 1" AIR GAP, LISTING FOR BACKFLOW PROTECTION OR CORRECT BACKFLOW PROTECTION FOR CHEMICAL ADDITION FOR WASHING MACHINES
3) INSTALL CLEANOUT UNIT #135
4) PROVIDE APPROVED WATER SUPPLY MATERIAL FOR JUICE MACHINE & COFFEE MAKER
5) COMPLETE GAS PIPING TO FIREPLACE
09/04/2009 PLUMBING - FINAL Partial Approval CHLORINIZATION AND BACTERIA REPORTS ACCEPTED
09/03/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
ROOF TOP PAINT VENT TERMINATIONS
3RD LEVEL ALL AREAS OK
2ND LEVEL ALL AREAS EXCEPT LAUNDRY FLOOR DRAIN TO BE FLUSH WITH FINISH FLOOR
1ST LEVEL WATER HEATERS OK

LOBBY - COMPLETE GAS TO FIREPLACE
TERMINATE EXTERIOR CLEANOUTS (3) TO GRADE MADE GAS TIGHT

100 - COMPLETE TUB AND SHOWER
101 - COMPLETE TUB AND SHOWER
103 - COMPLETE TUB AND SHOWER
108 - COMPLETE LAV AND TUB AND SHOWER
109 - COMPLETE SHOWER
110 - COMPLETE TUB & SHOWER
123 - LAUNDRY WASHERS NEED DRAINS CONNECTION TO TRENCH DRAIN
126 - LAUNDRY UNISEX RESTROOM OK
131 - COMPLETE CLOSET SEAT, COMPLETE SHOWER

140 OK
129 OK
112 OK
107 OK
106 OK
105 OK
104 OK
102 OK
137 OK
PANTRY AND PREP 114 & 115 OK

138 - NEED TUB & SHOWER WALL COMPLETION
135 - COMPLETE ALL INSTALLS OF PLUMBING
133 - COMPLETE SHOWER INSTALL
136 - COMPLETE TUB & SHOWER TRIM
134 - COMPLETE SHOWER TRIM AND WALLS
132 - COMPLETE SHOWER TRIM AND WALLS
09/02/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) 1ST LEVEL GANG RESTROOM
2) EXPOSE ALL CLEANOUTS THAT ARE REQUIRED PER PLAN
3) PROVIDE LOCATION OF WATER HAMMER ARRESTORS
NOTE:
1) COMPLETE WORK IN AN AREA BEFORE ASKING FOR INSPECTION. AS AGREED I WILL BE GLAD TO INSPECT 1/2 OF A FLOOR AT A TIME AS LONG AS IT IS COMPLETE
INSPECTION STOPPED
08/31/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) RECEIVED OK FOR HWR TO FEED 140 DEGREE COLD WATER SYSTEM FROM 120 DEGREE SYSTEM
08/28/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
08/27/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PREP AREA:
1) PROVIDE FULL SIZE PIPE TO CORRECT BACKFLOW PROTECTION FOR WATER TO TURBO FAN OVEN
2) PROVIDE PVC PRIMER FOR PVC DRAINAGE PIPING
3) PROVIDE LISTING FOR DISHWASHER FOR PROTECTION OF WATER SUPPLY FOR CHEMICAL ADDITION AT DISHWASHER OR CORRECT BACKFLOW PROTECTION
MECHANICAL ROOM:
1) HOT WATER RETURN FOR 120 DEGREE SYSTEM REQUIRES CHECK VALVE TO PREVENT HOT WATER RETURN FROM GOING TO 160 DEGREE WATER HEATER COLD SUPPLY SYSTEM
08/21/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) 2ND LEVEL ROOM FIXTURES OK, EXCEPT #220 AND 231
2) LAUNDRY NEEDS FLOOR DRAIN TERMINATION
3) VENDING NEEDS FLOOR SINK ,DOME, STRAINER AND CORRECT ICE MACHINE INSTALL
08/20/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED
08/19/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) 3RD LEVEL ALL ROOMS FIXTURES EXCEPT UNIT 320 & 331 OK
2) UNIT 344 VENDING MAY REQUIRE BACKFLOW PROTECTION FOR ICE MACHINE AND STRAINER AND DOME IN FLOOR SINK
08/07/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WATER TO BE ON TO ALL FIXTURES 3RD LEVEL
2) THEIR CAN ONLY BE ONE SLIP NUT CONNECTION BETWEEN WEIR OF TRAP AND DRAIN (AT THE WALL)
3) LIST IS NOT COMPLETE, PLEASE WALK THE FLOOR PRIOR TO CALLING IN FOR INSPECTION
08/06/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
07/30/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*