Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T08CM00837
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/15/2009 | PLUMBING - FINAL | Approved | ||
09/14/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) MAKE TUB AND SHOWER ENCLOSURE WATER TIGHT UNITS #109 & 136 2) PROVIDE PROOF OF 1" AIR GAP, LISTING FOR BACKFLOW PROTECTION OR CORRECT BACKFLOW PROTECTION FOR CHEMICAL ADDITION FOR WASHING MACHINES 3) INSTALL CLEANOUT UNIT #135 4) PROVIDE APPROVED WATER SUPPLY MATERIAL FOR JUICE MACHINE & COFFEE MAKER 5) COMPLETE GAS PIPING TO FIREPLACE |
|
09/04/2009 | PLUMBING - FINAL | Partial Approval | CHLORINIZATION AND BACTERIA REPORTS ACCEPTED | |
09/03/2009 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* ROOF TOP PAINT VENT TERMINATIONS 3RD LEVEL ALL AREAS OK 2ND LEVEL ALL AREAS EXCEPT LAUNDRY FLOOR DRAIN TO BE FLUSH WITH FINISH FLOOR 1ST LEVEL WATER HEATERS OK LOBBY - COMPLETE GAS TO FIREPLACE TERMINATE EXTERIOR CLEANOUTS (3) TO GRADE MADE GAS TIGHT 100 - COMPLETE TUB AND SHOWER 101 - COMPLETE TUB AND SHOWER 103 - COMPLETE TUB AND SHOWER 108 - COMPLETE LAV AND TUB AND SHOWER 109 - COMPLETE SHOWER 110 - COMPLETE TUB & SHOWER 123 - LAUNDRY WASHERS NEED DRAINS CONNECTION TO TRENCH DRAIN 126 - LAUNDRY UNISEX RESTROOM OK 131 - COMPLETE CLOSET SEAT, COMPLETE SHOWER 140 OK 129 OK 112 OK 107 OK 106 OK 105 OK 104 OK 102 OK 137 OK PANTRY AND PREP 114 & 115 OK 138 - NEED TUB & SHOWER WALL COMPLETION 135 - COMPLETE ALL INSTALLS OF PLUMBING 133 - COMPLETE SHOWER INSTALL 136 - COMPLETE TUB & SHOWER TRIM 134 - COMPLETE SHOWER TRIM AND WALLS 132 - COMPLETE SHOWER TRIM AND WALLS |
|
09/02/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) 1ST LEVEL GANG RESTROOM 2) EXPOSE ALL CLEANOUTS THAT ARE REQUIRED PER PLAN 3) PROVIDE LOCATION OF WATER HAMMER ARRESTORS NOTE: 1) COMPLETE WORK IN AN AREA BEFORE ASKING FOR INSPECTION. AS AGREED I WILL BE GLAD TO INSPECT 1/2 OF A FLOOR AT A TIME AS LONG AS IT IS COMPLETE INSPECTION STOPPED |
|
08/31/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) RECEIVED OK FOR HWR TO FEED 140 DEGREE COLD WATER SYSTEM FROM 120 DEGREE SYSTEM |
|
08/28/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/27/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PREP AREA: 1) PROVIDE FULL SIZE PIPE TO CORRECT BACKFLOW PROTECTION FOR WATER TO TURBO FAN OVEN 2) PROVIDE PVC PRIMER FOR PVC DRAINAGE PIPING 3) PROVIDE LISTING FOR DISHWASHER FOR PROTECTION OF WATER SUPPLY FOR CHEMICAL ADDITION AT DISHWASHER OR CORRECT BACKFLOW PROTECTION MECHANICAL ROOM: 1) HOT WATER RETURN FOR 120 DEGREE SYSTEM REQUIRES CHECK VALVE TO PREVENT HOT WATER RETURN FROM GOING TO 160 DEGREE WATER HEATER COLD SUPPLY SYSTEM |
|
08/21/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) 2ND LEVEL ROOM FIXTURES OK, EXCEPT #220 AND 231 2) LAUNDRY NEEDS FLOOR DRAIN TERMINATION 3) VENDING NEEDS FLOOR SINK ,DOME, STRAINER AND CORRECT ICE MACHINE INSTALL |
|
08/20/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELED |
|
08/19/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) 3RD LEVEL ALL ROOMS FIXTURES EXCEPT UNIT 320 & 331 OK 2) UNIT 344 VENDING MAY REQUIRE BACKFLOW PROTECTION FOR ICE MACHINE AND STRAINER AND DOME IN FLOOR SINK |
|
08/07/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER TO BE ON TO ALL FIXTURES 3RD LEVEL 2) THEIR CAN ONLY BE ONE SLIP NUT CONNECTION BETWEEN WEIR OF TRAP AND DRAIN (AT THE WALL) 3) LIST IS NOT COMPLETE, PLEASE WALK THE FLOOR PRIOR TO CALLING IN FOR INSPECTION |
|
08/06/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/30/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |