Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T08CM00837

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
08/21/2009 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
08/19/2009 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) TEST FROM METER LOCATION TO SHUT OFF VALVES AT REGULATORS OK
2) PROVIDE LOW PRESSURE TEST TO UNIT VALVES
08/13/2009 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) PLEASE SEE DETAIL #3 PAGE P4.0 FOR GAS VALVES
2) REVISED APPROVED PLAN ON SITE
04/08/2009 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
60 PSI TEST FROM METER LOCATION TO VALVES PRIOR TO REGULATORS AND TO GANG WATER HEATERS, SINGLE WATER HEATER AND DRYERS PER REDLINE ON SITE, CITY FO TUCSON APPROVAL REQUIRED FOR REVISIONS TO GAS SYSTEM.
04/06/2009 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
TEST ON PIPING TO MEET REQUIREMENTS OF
SECTION 1214.3.1 OF 2006 C.O.T LOCAL AMENDMENTS TO
2006 UPC

INSTALL GAS PIPING PER PLAN SIZING OK
PROVIDE REDLINE ON SITE WITH CITY APPROVED REVISION TO FOLLOW FOR GAS SYSTEM.