Permit: T08CM00837

Parcel: 13423424B


Addresses:

251 S WILMOT RD

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
04/07/2009 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
03/09/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1. XR501 4" COUPLING BETWEEN SDR AND SCH80 4" PVC
TIED INTO BLDG. WITH 4" COMPANION FLANGE OK
OK TO COVER
2. 2 - 3" LEAK REPAIRED OK FROM 3/5/09
02/25/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
TEST 200 PSI FROM METER ASSEMBLY TO BLDG. OK
1. NEED TO SEE FINAL CONNECTION AT BLD. WITH TEST
02/24/2009 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
02/20/2009 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE TEST ON PIPING
02/19/2009 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
TIE IN AT METER THRU RPB OK
WILL NEED TO SEE TEST AND TIE IN AT BLD. OF YARD PIPING
02/13/2009 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSTALL BACKFLOW PROTECTION DEVICE, PROPERLY WRAP DUCTILE FITTINGS AND PROVIDE TESTING.
11/25/2008 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
4" C-900 PER TUCSON WATER STANDARDS, WITH RESTRAINTS AND NO 90 DEG. TURNS YET, PER INITIAL PAGE 1 OF 1 SITE PLAN IN TRAILER, COMPLETION WITH HYDROSTATIC TEST LATER DATE - OK TO COVER THIS SECTION.

1. EXPOSE COPPER BLD. RISER AND PROVIDE TEST ON THIS PIPING AT LATER DATE.
11/24/2008 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :