Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T08CM00837
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2009 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
03/09/2009 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1. XR501 4" COUPLING BETWEEN SDR AND SCH80 4" PVC TIED INTO BLDG. WITH 4" COMPANION FLANGE OK OK TO COVER 2. 2 - 3" LEAK REPAIRED OK FROM 3/5/09 |
|
02/25/2009 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* TEST 200 PSI FROM METER ASSEMBLY TO BLDG. OK 1. NEED TO SEE FINAL CONNECTION AT BLD. WITH TEST |
|
02/24/2009 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* | |
02/20/2009 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE TEST ON PIPING |
|
02/19/2009 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* TIE IN AT METER THRU RPB OK WILL NEED TO SEE TEST AND TIE IN AT BLD. OF YARD PIPING |
|
02/13/2009 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSTALL BACKFLOW PROTECTION DEVICE, PROPERLY WRAP DUCTILE FITTINGS AND PROVIDE TESTING. |
|
11/25/2008 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 4" C-900 PER TUCSON WATER STANDARDS, WITH RESTRAINTS AND NO 90 DEG. TURNS YET, PER INITIAL PAGE 1 OF 1 SITE PLAN IN TRAILER, COMPLETION WITH HYDROSTATIC TEST LATER DATE - OK TO COVER THIS SECTION. 1. EXPOSE COPPER BLD. RISER AND PROVIDE TEST ON THIS PIPING AT LATER DATE. |
|
11/24/2008 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection : |