Permit: T08CM00837

Parcel: 13423424B


Addresses:

251 S WILMOT RD


Inspection Status: Approved

Inspection History: PLUMBING - ROOF DRAINS

Permit Number - T08CM00837

Inspection Description - PLUMBING - ROOF DRAINS

Inspection Status - Approved

Date Description Inspector Results Comments
08/31/2009 PLUMBING - ROOF DRAINS Approved IVRS - Inspection :*
08/28/2009 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR CANCELLED
04/09/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
CANOPY DRAINS SUPPORTS OK (PARTIAL APPROVAL)
04/06/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
3" RD & OFRD's (4) AT FRONT ENTRANCE WATER TEST OK

1. SUPPORT ARM OVER AT DRAIN BODIES
03/05/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
NEED FRONT ENTRY CANOPY RAIN DRAINAGE TESTING AND CORRECTION TO MAIN ROOF FOR PENDING AT RAIN DRAIN LOCATIONS.
03/04/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
ALL RAIN DRAINS MAIN BLD. WATER TEST AND SUPPORTS OK

1. NEED CANOPY RAIN DRAIN INSPECTION AND ROOF CORRECTION FOR PENDING AT RAIN DRAIN LOCATIONS.
03/02/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
RAIN DRAIN AND OVERFLOW DRAIN PIPING WATER TEST PER INITIAL PAGE P1.4

1. PROVIDE CORRECT SUPPORT AT ROOF LEVEL
REPAIR LEAK AT 348 SQ.FT. ROOF 90 DEG.
02/27/2009 PLUMBING - ROOF DRAINS Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/25/2009 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
WATER TEST ROOF DRAINS PER INITIAL PAGE P1.4
1. ALL ROOF DRAINS REQUIRE CORRECT SUPPORTS
ROOF DRAINS AT ALL (4) CORNERS OF BUILDING ARE NOT IN CORRECT LOCATION TO DRAIN ROOF STRUCTURE AND REQUIRE ROOF OR LOCATION CHANGE
11/05/2008 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1. POST AN ADDRESS FOR YOUR JOB SITE
2. WATER TEST ALL RAIN DRAINS FROM 4' BLD. EXTERIOR UP INSIDE BLD. TO 3" AFF