Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
Permit Number - T08CM00837
Inspection Description - PLUMBING - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2009 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/06/2009 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) 3RD LEVEL OK |
|
07/30/2009 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) 1ST LEVEL INSULATION NEEDS TO BE COMPLETED AND CONTINOUS ON PIPING 2) ABANDONED COPPER STUBS NEED TO BE SMOKE/FIRE STOPPED |
|
07/23/2009 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
07/22/2009 | PLUMBING - ABOVE CEILING | Partial Approval | 1) 3RD LEVEL HOT RETURN INSULATION NEED COMPLETION AND PIPING REQUIRES CORRECT SUPPORT 2) 2ND LEVEL ABOVE CEILING-OK |
|
02/13/2009 | PLUMBING - ABOVE CEILING | Denied | CONTRACTOR TO PAY REINSPECTION FEE TEST ON DWV TO BE FREE OF LEAKS WITH SUPPORTS, FHA STRAPS, PROTECTION PLATES, REDLINES TO BE ON SITE AT TIME OF INSPECTION. |