Permit: T08CM00837

Parcel: 13423424B


Addresses:

251 S WILMOT RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM00837

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/21/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/30/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ALL LEVELS CLOSET FLANGES-OK
07/22/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/22/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SHOWER BASES ARE OK
06/25/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD LEVEL CLOSET FLANGES OK
06/24/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD LEVEL FROM ROOMS #314 & 315
EAST CLOSET FLANGES OK
06/18/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 2ND LEVEL CLOSET FLANGES-OK
06/11/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
THIS INSPECTION FOR 2ND LEVEL CLOSET FLANGES OK
EXCEPT UNITS #214, 219, 232 -- PLEASE COMPLETE WORK AS DISCUSSED OK -- YOU WILL BE ASSESSED REINSPECTION FEE
06/09/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
UNIT #140 REQUIRES AN APPROVED OFFSET CLOSET FLANGE THAT IS APPROVED FOR THE INSTALLATION IT IS USED FOR
ALL CLOSET FLANGES TO BE PROPERLY SECURED TO FLOOR.
04/09/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
ALL TUBS DRAINAGE OK
LEVEL 1 TUB BOXES OK
LEVEL 2 & 3 TUB DRAINS SEALED AT FLOOR LEVEL
04/08/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
-- TEST ON TUBS ALL AREAS EXCEPT
LEVEL 1 UNITS 137, 138, 139, 140
-- TUBS ON LEVEL 1 REQUIRE SEAL OF TUB BOX WITH INSPECTION
04/07/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD LEVEL TUBS TEST ALL EXCEPT UNITS #312
2ND LEVEL TUBS TEST ALL EXCEPT UNITS #219 & 239

NOTE: LEVEL 3 & 2 REQUIRE INSPECTION OF SEAL OFF OF PIPE PENETRATION THRU FLOOR CEILING ASSEMBLY PRIOR TO COVERING.
04/06/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. TUBS TO DRAIN FROM OVERFLOW & DRAIN WITHOUT LEAKS
2. TUB AND SHOWER VALVES TO BE SECURE
03/19/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV THRU ROOF ALL AREAS OK
WATER DISTRIBUTION ALL AREAS EXCEPT 1ST & 3RD
LEVEL CORRIDORS AND MECHANICAL ROOM OK
03/17/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
2ND LEVEL IN WALL AND OVERHEAD OK
03/11/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. NO PORTION OF ANY WORK MAY BE CONCEALED UNTIL IT HAS BEEN INSPECTED AND APPROVED (ONE SIDING OK, BATT INSULATION CONCEALING PIPES IS NOT)
2. 2006 IECC REQUIRES THAT ALL HOT AND HOT RETURN PIPING IS TO BE INSULATED. IT DOES NOT DIFFERENTIATE MAINS FROM BRANCHES
3. OK TO START INSULATING HOT AND RETURN PIPING ON
2ND AND 3RD FLOOR - PLEASE UNCOVER ALL CONCEALED PIPING
03/09/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/05/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV TEST THRU ROOF ALL AREAS EXCEPT BREAKROOM 125
3" CLEANOUT LEAKS LOWER SIDE OR FROM UNDER SLAB NEEDS RETEST AND TUBS & SHOWERS NEED OVERFLOW DRAIN AND RUN TEST FOR DRAINAGE CONNECTIONS.
WATER DISTRIBUTION WITH INSULATION LEVEL 1 IN
ROOMS OK PER ENGINEER DIRECTIVE FOR INSULATION NOT PER PLAN SPEC.
03/04/2009 PLUMBING - INTERMEDIATE Partial Approval - 1st LEVEL WATER DISTRIBUTION FOR ROOMS AND MAINS WATER TEST OK
- 1st LEVEL WATER ONLY NEEDS INSULATION PER ENGINEERS
DIRECTIVE WITH INSPECTION FOR (PLUMBING OK FOR SHEETROCK)
03/02/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
ALL PIPING TO BE INSULATED PER P0.0 SECTION 2.3
WATER DISTRIBUTION LEVEL 1 ONLY FROM 4" IN MECH. ROOM VALVES, THRU TO STUB UP TO LEVEL 2 TEST OK
1. REPAIR LEAKS ON MAIN IN HALLWAY OVERHEAD
2. SUPPORT TUBING AND MANIFOLD DISTRIBUTION DEVICES
3. SUPPORT ALL TRAP PRIMERS VALVES AND DISTRIBUTION DEVICES PLUMB & LEVEL
4. PROVIDE TUBING ISOLATORS THRU BOARD HOLES
02/27/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
FAILURE TO BE READY AT TIME OF INSPECTION, IN THE FUTURE WILL RESULT IN REINSPECTION FEES
02/25/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
PROVIDE REDLINES OF YOUR CHANGES
TO DWV SYSTEM ON SITE
02/24/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
MET WITH DALCO ABOUT SITE SEWER TO BE INSPECTED PER PIMA COUNTY STAMP

DWV THRU ROOF WATER TEST FROM UNIT #120 EAST AND UNIT #110 EAST TO END OF BLD.
02/19/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER TEST DWV THRU ROOF UNITS 120, 117, 118, 129 AND ABOVE EXCEPT UNIT #117 & 118 REQUIRES VENT FOR FLOOR DRAINS UNIT #225 REQUIRES STOOL VENT, UNIT #152 DRAIN NEEDS MINIMUM 1/4" PER FOOT FALL, UNITS 110, 160, 159, 158, 154, 148, 116, 115 THRU 132 DWV THRU ROOF
WATER TEST OK EXCEPT CORRECTIONS ABOVE
02/13/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/10/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/09/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER TEST DWV UNITS 131, 133, 135, 137, 139, 141 THRU ROOF EXCEPT UNIT #235 SHOWER DRAIN REQUIRES CORRECT VENTING OF SHOWER. PROVIDE SAFETY PLATES AND FHA STRAPS AS REQUIRED IN ALL UNITS. UNIT #223 TGI NEEDS REPAIR FOR LEVEL 3
02/06/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/05/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER TEST UNITS 132, 134, 136, 138, 140
DWV 1ST THRU ROOF OK
UNIT #132, 232, 332 REQUIRES ENGINEER DIRECTIVE FOR REPAIR TO TGI AT STOOL PENETRATION THRU TGI WITH CORRECT FIRE RATED ASSEMBLY
02/04/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
TEST TO BE IN PLACE WITH NO LEAKS
SANDY @ 837-2214
01/28/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*