Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T08CM00837
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2009 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/30/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ALL LEVELS CLOSET FLANGES-OK |
|
07/22/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/22/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SHOWER BASES ARE OK |
|
06/25/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 3RD LEVEL CLOSET FLANGES OK |
|
06/24/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 3RD LEVEL FROM ROOMS #314 & 315 EAST CLOSET FLANGES OK |
|
06/18/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 2ND LEVEL CLOSET FLANGES-OK |
|
06/11/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* THIS INSPECTION FOR 2ND LEVEL CLOSET FLANGES OK EXCEPT UNITS #214, 219, 232 -- PLEASE COMPLETE WORK AS DISCUSSED OK -- YOU WILL BE ASSESSED REINSPECTION FEE |
|
06/09/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* UNIT #140 REQUIRES AN APPROVED OFFSET CLOSET FLANGE THAT IS APPROVED FOR THE INSTALLATION IT IS USED FOR ALL CLOSET FLANGES TO BE PROPERLY SECURED TO FLOOR. |
|
04/09/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ALL TUBS DRAINAGE OK LEVEL 1 TUB BOXES OK LEVEL 2 & 3 TUB DRAINS SEALED AT FLOOR LEVEL |
|
04/08/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* -- TEST ON TUBS ALL AREAS EXCEPT LEVEL 1 UNITS 137, 138, 139, 140 -- TUBS ON LEVEL 1 REQUIRE SEAL OF TUB BOX WITH INSPECTION |
|
04/07/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 3RD LEVEL TUBS TEST ALL EXCEPT UNITS #312 2ND LEVEL TUBS TEST ALL EXCEPT UNITS #219 & 239 NOTE: LEVEL 3 & 2 REQUIRE INSPECTION OF SEAL OFF OF PIPE PENETRATION THRU FLOOR CEILING ASSEMBLY PRIOR TO COVERING. |
|
04/06/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. TUBS TO DRAIN FROM OVERFLOW & DRAIN WITHOUT LEAKS 2. TUB AND SHOWER VALVES TO BE SECURE |
|
03/19/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV THRU ROOF ALL AREAS OK WATER DISTRIBUTION ALL AREAS EXCEPT 1ST & 3RD LEVEL CORRIDORS AND MECHANICAL ROOM OK |
|
03/17/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2ND LEVEL IN WALL AND OVERHEAD OK |
|
03/11/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NO PORTION OF ANY WORK MAY BE CONCEALED UNTIL IT HAS BEEN INSPECTED AND APPROVED (ONE SIDING OK, BATT INSULATION CONCEALING PIPES IS NOT) 2. 2006 IECC REQUIRES THAT ALL HOT AND HOT RETURN PIPING IS TO BE INSULATED. IT DOES NOT DIFFERENTIATE MAINS FROM BRANCHES 3. OK TO START INSULATING HOT AND RETURN PIPING ON 2ND AND 3RD FLOOR - PLEASE UNCOVER ALL CONCEALED PIPING |
|
03/09/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/05/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV TEST THRU ROOF ALL AREAS EXCEPT BREAKROOM 125 3" CLEANOUT LEAKS LOWER SIDE OR FROM UNDER SLAB NEEDS RETEST AND TUBS & SHOWERS NEED OVERFLOW DRAIN AND RUN TEST FOR DRAINAGE CONNECTIONS. WATER DISTRIBUTION WITH INSULATION LEVEL 1 IN ROOMS OK PER ENGINEER DIRECTIVE FOR INSULATION NOT PER PLAN SPEC. |
|
03/04/2009 | PLUMBING - INTERMEDIATE | Partial Approval | - 1st LEVEL WATER DISTRIBUTION FOR ROOMS AND MAINS WATER TEST OK - 1st LEVEL WATER ONLY NEEDS INSULATION PER ENGINEERS DIRECTIVE WITH INSPECTION FOR (PLUMBING OK FOR SHEETROCK) |
|
03/02/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ALL PIPING TO BE INSULATED PER P0.0 SECTION 2.3 WATER DISTRIBUTION LEVEL 1 ONLY FROM 4" IN MECH. ROOM VALVES, THRU TO STUB UP TO LEVEL 2 TEST OK 1. REPAIR LEAKS ON MAIN IN HALLWAY OVERHEAD 2. SUPPORT TUBING AND MANIFOLD DISTRIBUTION DEVICES 3. SUPPORT ALL TRAP PRIMERS VALVES AND DISTRIBUTION DEVICES PLUMB & LEVEL 4. PROVIDE TUBING ISOLATORS THRU BOARD HOLES |
|
02/27/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* FAILURE TO BE READY AT TIME OF INSPECTION, IN THE FUTURE WILL RESULT IN REINSPECTION FEES |
|
02/25/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PROVIDE REDLINES OF YOUR CHANGES TO DWV SYSTEM ON SITE |
|
02/24/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* MET WITH DALCO ABOUT SITE SEWER TO BE INSPECTED PER PIMA COUNTY STAMP DWV THRU ROOF WATER TEST FROM UNIT #120 EAST AND UNIT #110 EAST TO END OF BLD. |
|
02/19/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER TEST DWV THRU ROOF UNITS 120, 117, 118, 129 AND ABOVE EXCEPT UNIT #117 & 118 REQUIRES VENT FOR FLOOR DRAINS UNIT #225 REQUIRES STOOL VENT, UNIT #152 DRAIN NEEDS MINIMUM 1/4" PER FOOT FALL, UNITS 110, 160, 159, 158, 154, 148, 116, 115 THRU 132 DWV THRU ROOF WATER TEST OK EXCEPT CORRECTIONS ABOVE |
|
02/13/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
02/10/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
02/09/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER TEST DWV UNITS 131, 133, 135, 137, 139, 141 THRU ROOF EXCEPT UNIT #235 SHOWER DRAIN REQUIRES CORRECT VENTING OF SHOWER. PROVIDE SAFETY PLATES AND FHA STRAPS AS REQUIRED IN ALL UNITS. UNIT #223 TGI NEEDS REPAIR FOR LEVEL 3 |
|
02/06/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
02/05/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER TEST UNITS 132, 134, 136, 138, 140 DWV 1ST THRU ROOF OK UNIT #132, 232, 332 REQUIRES ENGINEER DIRECTIVE FOR REPAIR TO TGI AT STOOL PENETRATION THRU TGI WITH CORRECT FIRE RATED ASSEMBLY |
|
02/04/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* TEST TO BE IN PLACE WITH NO LEAKS SANDY @ 837-2214 |
|
01/28/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |