Permit: T08CM00837

Parcel: 13423424B


Addresses:

251 S WILMOT RD

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
11/24/2008 ELECTRIC - UFER Approved IVRS - Inspection :*
11/21/2008 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/27/2008 ELECTRIC - UFER Denied IVRS - Inspection :
The grounding electrode conductor is not installed per code.| 220*
UFER IS TO BE CONNECTED TO BOTTOM REBAR IN FOUNDATION OR FOOTING 250.50 & 64
10/24/2008 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR