Permit: T08CM00835

Parcel: 120085120


Addresses:

4841 S 12TH AV

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
07/13/2010 MECHANICAL - HOODS Approved IVRS - Inspection :*
07/09/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) HEAT SENSOR INTERLOCK NOT WORKING, ALL OTHER CORRECTIONS MADE
06/22/2010 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
1) GREASE DUCT TERMINATION NOT ATTACHED TO CURB
2) PROVIDE PROPER CLEARANCE TO WASTE VENT FROM M.V.A.
3) PROVIDE SMOKE CONTAINMENT TEST
4) PROVIDE HEAT SENSOR INTERLOCK TEST
5) PROVIDE GREASE RECEPTORS UNDERHOOD
6) PROVIDE FILTERS INSTALLED IN HOOD
7) EXHAUST/MAKE UP AIR INTERLOCK OK
8) PAINT ALL PLASTIC VENT PIPING EXPOSED TO U.V. LIGHT
9) PROVIDE MINIMUM TO COMBUSTIBLES AT W/H B-VENT
03/19/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) FINISH FLASHING AND CAULK AROUND HOOD-COMPLETE HOOD SYSTEMS
2) WATER HEATER VENT TO CLOSE TO COOLER
3) WASTE VENT TO CLOSET TO COOLER
01/25/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) SECOND LAYER FIRE WRAP OK
2) INSTALL ? SENSOR PRIOR TO HANGING HOOD
01/22/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) 1ST LAYER OF FIREWRAP OK
01/21/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) GREASE DUCT SMOKE TEST OK, OK FOR 1ST LAYER OF FIRE WRAP
12/02/2009 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*