Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2010 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 07/09/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) HEAT SENSOR INTERLOCK NOT WORKING, ALL OTHER CORRECTIONS MADE |
|
| 06/22/2010 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* 1) GREASE DUCT TERMINATION NOT ATTACHED TO CURB 2) PROVIDE PROPER CLEARANCE TO WASTE VENT FROM M.V.A. 3) PROVIDE SMOKE CONTAINMENT TEST 4) PROVIDE HEAT SENSOR INTERLOCK TEST 5) PROVIDE GREASE RECEPTORS UNDERHOOD 6) PROVIDE FILTERS INSTALLED IN HOOD 7) EXHAUST/MAKE UP AIR INTERLOCK OK 8) PAINT ALL PLASTIC VENT PIPING EXPOSED TO U.V. LIGHT 9) PROVIDE MINIMUM TO COMBUSTIBLES AT W/H B-VENT |
|
| 03/19/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) FINISH FLASHING AND CAULK AROUND HOOD-COMPLETE HOOD SYSTEMS 2) WATER HEATER VENT TO CLOSE TO COOLER 3) WASTE VENT TO CLOSET TO COOLER |
|
| 01/25/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) SECOND LAYER FIRE WRAP OK 2) INSTALL ? SENSOR PRIOR TO HANGING HOOD |
|
| 01/22/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) 1ST LAYER OF FIREWRAP OK |
|
| 01/21/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) GREASE DUCT SMOKE TEST OK, OK FOR 1ST LAYER OF FIRE WRAP |
|
| 12/02/2009 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* |