Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T08CM00835

Parcel: 120085120


Addresses:

4841 S 12TH AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/29/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
06/22/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) COMPLETE #23 FROM PLUMBING SPEC
2) PROVIDE SUPPORT AND PAINT FOR VENTS
3) PROVIDE 10' FROM OR 3' ABOVE COOLER FOR INTERCEPTOR AND UNCOVER CLEANOUTS
06/14/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1 - COMPLETE #23 FOR PLUMBERS SPEC
2 - PROVIDE APPROVED BACKFLOW PROTECTION FOR LANDSCAPING IN FRONT & BACK OF BUILDING
3 - COMPLETE D?PING OF HAND SINKS
4 - ADD SUPPORT ON EXPANSION TANK
5 - PROVIDE SUPPORT ON DRAIN PIPING FROM 3 COMPARTMENT SINK